Master Electrician Exam 2025 – 400 Free Practice Questions to Pass the Exam

Question: 1 / 400

What is the maximum standard size overcurrent protection device permitted on the primary side of a 50 kVA transformer with a 480-volt, 3-phase primary?

80 amperes

100 amperes

125 amperes

150 amperes

To determine the maximum standard size overcurrent protection device permitted on the primary side of a 50 kVA transformer with a 480-volt, 3-phase primary, one must first calculate the full-load current of the transformer. The formula used is:

Full-load current (I) = kVA × 1000 / (Voltage × √3)

For a 50 kVA transformer at 480 volts, the calculation would be:

I = 50 × 1000 / (480 × √3)

Calculating √3 gives approximately 1.732, thus:

I = 50000 / (480 × 1.732)

I ≈ 50000 / 831.36

I ≈ 60.1 amperes

According to the National Electrical Code (NEC), for transformers, overcurrent protection on the primary side can be sized larger than the full-load current by using the 125% rule for overcurrent protection for transformers rated above 9 kVA.

Thus, the size of the overcurrent protection device can be calculated as follows:

125% of full-load current = 1.25 × 60.1 amperes ≈ 75.125 amperes

The next step is

Get further explanation with Examzify DeepDiveBeta
Next Question

Report this question

Subscribe

Get the latest from Examzify

You can unsubscribe at any time. Read our privacy policy